Home › PFAS › DE

PFAS in drinking water: Delaware

EPA UCMR 5 results for 36 public water systems. 17 had at least one PFAS detected; 14 had a highest single PFOA or PFOS result above 4.0 ppt.

UCMR 5 is a one-time EPA monitoring program, not a compliance determination. The values shown are the highest single sample result at any of the system's sampling points; one result above 4.0 ppt does not mean the system violates the PFAS rule, which is judged on running annual averages under separate compliance monitoring. Results describe the public water system, not an individual home.

Water systemServesPFOA max (ppt)PFOS max (ppt)PFAS detected
Artesian Northern Sussex Regional
DE0020003
Lewes5.7ND4
Artesian Water Company
DE0000552
Bear, Hockessin23.168
Bayside Pump District
DE00A0837
Fenwick IslandNDND3
Bethany Bay Pump District
DE0000221
MillvilleND6.11
Bethany Beach Water Department
DE0000556
Bethany BeachNDND0
Bridgeville Water Department
DE0000559
BridgevilleNDND0
Camden Pump District
DE0000124
Camden-WyomingNDND0
Camden Wyoming Sewer and Water Authority
DE0000563
Camden-WyomingNDND0
Church Creek
DE00A0428
MagnoliaNDND0
Delmar Utility Comm (TN of Delmar)
DE0000567
DelmarNDND0
Dewey Beach Water Department
DE0000825
Dewey Beach11ND5
Dover Air Force Base
DE0000579
Dover AfbNDND0
Dover Water Department
DE0000571
DoverNDND0
East NCC District
DE00A0334
OdessaNDND0
Garrison Lake Pump District
DE0000004
SmyrnaNDND0
Georgetown Water Department
DE0000592
Georgetown361411
Laurel Water Department
DE0000597
LaurelNDND0
Lewes Board of Public Works
DE0000602
Lewes6.19.53
Long Neck Water Company
DE0000625
MillsboroNDND0
Meadows Pump District
DE0000271
MillsboroNDND0
Middletown Water Department, De
DE0000614
MiddletownNDND0
Milford Water Department
DE0000616
MilfordNDND0
Millsboro Water Department
DE0000622
MillsboroNDND0
Municipal Services Commission
DE0000634
New CastleNDND2
Newark Water Department, De
DE0000630
Newark25.37.58
North West Pump District
DE00A0347
MiddletownNDND0
Rehoboth Beach Water Department
DE0000723
Rehoboth Beach14.96.27
Rehoboth Pump District
DE0000991
Rehoboth Beach4.4ND4
Seaford Water Department
DE0000246
SeafordNDND2
Smyrna Water Department
DE0000657
Smyrna9.86.75
South Bethany
DE00A0323
Bethany BeachND4.71
Stage Village MHC
DE0000569
Delmar7.68.55
Suez Water Delaware
DE0000564
New Castle, Wilmington24.4ND9
Sussex Shores Water Company
DE0000557
Bethany BeachNDND0
Swann Keys
DE0000465
Fenwick IslandNDND0
Wilmington Water Department
DE0000663
Wilmington9.9ND6

ND = not detected (below the 4 ppt UCMR 5 reporting level). Values are the highest single sample result, not an annual average.

Source: EPA UCMR 5 final occurrence data (EPA page last updated 2026-08-28; samples collected January 2023 – December 2025) ↗.

PFAS disclaimer: PFAS results are copied from EPA's UCMR 5 dataset and describe samples taken at a public water system's entry points between 2023 and 2025, not water at any specific address. Levels may have changed since sampling (for example, after new treatment). “Not detected” means below EPA's UCMR 5 minimum reporting level, not zero. This is not a compliance determination or a water test. Contact your water utility for current information.